Eaton's Cooper Power series Edison capacitor and Type NR oil switches are primarily used for switching capacitor currents, but could also be used for inductive applications. The NR switch is motor-operated, whereas the Edison capacitor switch is solenoid-operated. Both switches include an integral operating handle for position indication or manual operation. Specialty applications are available.
| Rated maximum voltages (kV - LL) | 25 (ungrounded) 38 (grounded) |
| Current rating | 200A & 400A (15kv) |
| Mechanical operations (1 close and 1 open) | 50,000 |
| Temperature rating | -40 to +60°C |
| Short-time symmetrical withstand current (A) | 4,500 |
| Fault closing (A) | 6,000 |
| High frequency transient making peak current (A) | 9,000 (12,000 optional) |
| Basic Impulse Level (BIL) (kV) | 95-150 |
| Rated maximum voltages (kV - LL) | 22 (ungrounded) 34.5 (grounded) |
| Current rating | 60A & 200A (15kV) |
| Mechanical operations (1 close and 1 open) | 10,000 |
| Temperature rating | -40 to +46°C |
| Short-time symmetrical withstand current (A) | 4,500 |
| Fault closing (A) | 6,000 |
| High frequency transient making peak current (A) | 12,000 |
| Basic Insulation Level (BIL) | 95-125 kV |
| IEEE standards | C37.66 |
| IEC standards (applies to Edison capacitor switch only) | 60815-Part 1 (Bushing) 60815-Part 3 (Bushing) |
| Tank design | Non-metal fiberglass reinforced polyester |
| Manual trip | Integrated rain shield with visual trip indicator |
| Terminal orientation | 360-degree termination in 60 degree increments |
| Conductor cable range | #8 - 2/0 (standard) #6 - 350 MCM (optional) |
| Bushing | Cycloaliphatic epoxy bushing |
| Switch orientation | Horizontal and vertical mounting |
| Tank design | Painted mild formed steel (standard) Stainless steel (optional) Zinc plated (optional) |
| Manual trip | Sleet hood and operating handle with visual trip indicator |
| Terminal irientation | Vertical or horizontal |
| Conductor cable range | #8 - 2/0 |
| Bushing | Porcelain |
| Switch orientation | Vertical mounting only |
| Applications | Pole-mounted banks, open air banks (Externally Fused, Internally Fused, or Fuseless), metal-enclosed banks, mobile capacitor banks and specialty applications (HVDC, SVC, Series) |
| Control options | CBC-8000 capacitor control Valquest Z-Cap (Zero Voltage Closing) |
| Applications | Pole-mounted banks, open air banks (Externally Fused, Internally Fused, or Fuseless), metal-enclosed banks, mobile capacitor banks and specialty applications (HVDC, SVC, Series) |
| Control options | CBC-8000 capacitor control |